D3 Variable Air Volume Ceiling-Mounted Air Conditioning Unit
Product Category:
Keywords:
|
Standard operating conditions
|
Dry-bulb temperature
|
Wet-bulb temperature
|
Inlet water temperature
|
Water temperature difference
|
|
Return Air Cooling
|
27°C
|
19.5°C
|
7°C
|
5°C
|
|
Return Air Heating
|
21°C
|
——
|
60°C
|
——
|
|
Fresh Air Cooling
|
34°C
|
28°C
|
7°C
|
5°C
|
| Fresh Air Heating |
5°C
|
—— |
60°C
|
—— |
type Number
|
wind quantity
m 3/h
|
Cooling capacity
(KW)
|
Calories
(KW)
|
Water flow rate
(T/h)
|
Water resistance
(K/Pa)
|
Total pressure of the unit
(Pa)
|
Unit power
(KW)
|
Noise dB(A)
|
Operating weight
(Kg)
|
||||
Return wind
|
new wind
|
Return wind
|
new wind
|
Return wind
|
new wind
|
Return wind
|
new wind
|
||||||
FP-15D3
|
1500
|
8.72
|
19.4
|
14
|
22.9
|
1.5
|
3.3
|
7.95
|
22.5
|
100
|
0.32
|
<52
|
127
|
FP-20D3
|
2000
|
11.6
|
25.9
|
18.6
|
30.6
|
2
|
4.5
|
10.5
|
7.51
|
100
|
0.37
|
<52
|
142
|
FP-30D3
|
3000
|
17.4
|
38.8
|
27.9
|
45.8
|
3
|
6.7
|
17.3
|
12.5
|
100
|
0.64
|
<52
|
175
|
6 rows of tubes (6ROWS)
type Number
|
wind quantity
m 3/h
|
Cooling capacity
(KW)
|
Calories
(KW)
|
Water flow rate
(T/h)
|
Water resistance
(K/Pa)
|
Total pressure of the unit
(Pa)
|
Unit power
(KW)
|
Noise dB(A)
|
Operating weight
(Kg)
|
||||
Return wind
|
new wind
|
Return wind
|
new wind
|
Return wind
|
new wind
|
Return wind
|
new wind
|
||||||
FP-15D3
|
1500
|
11.8
|
24.2
|
18.8
|
27.3
|
2.02
|
4.1
|
14
|
28
|
60
|
0.32
|
<52
|
134
|
FP-20D3
|
2000
|
15.7
|
32.3
|
25.1
|
36.5
|
2.7
|
5.6
|
20.7
|
11.8
|
60
|
0.37
|
<52
|
149
|
FP-30D3
|
3000
|
23.3
|
48.4
|
37.2
|
54.7
|
4
|
8.3
|
36.5
|
20.7
|
60
|
0.64
|
<52
|
186
|
Size/Model
|
Width W (mm)
|
Deep W (mm)
|
High H (mm)
|
A
(mm)
|
B
(mm)
|
C
(mm)
|
D
(mm)
|
E
(mm)
|
F
(mm)
|
Inlet and outlet water DN (supply/return air, 4/6 rows) )
|
Drainage (DN)
|
|||
4H
|
6H
|
4X
|
6X
|
|||||||||||
FP-15D3
|
800
|
1050
|
540
|
460
|
720
|
122
|
270
|
265
|
/
|
25
|
25
|
32
|
32
|
25
|
FP-20D3
|
920
|
1050
|
540
|
460
|
840
|
228
|
260
|
330
|
/
|
25
|
25
|
32
|
32
|
25
|
FP-30D3
|
1300
|
1050
|
540
|
460
|
1220
|
122
|
270
|
205
|
350
|
25
|
32
|
40
|
40
|
25
|
“Due to space constraints, only a portion of the parameters is shown above. For detailed information, please refer to the following link:” “New Ya Air-Conditioning Equipment Electronic Catalog” ”
Product Inquiry
*Note: Please fill in the information accurately and keep the communication open. We will contact you as soon as possible.